An accredited service technician can be located by visiting our website at www.
greenwayhp.com or by calling our Customer Service Center at 1-866-253-0447.
WARNING: Never attempt to service the vitapur
®
UV system unless you are an
accredited service technician, as the performance of the system could be adversely
affected.
5.1 Lamp Installation and Replacement
WARNING: The lamp heats up after continuous use and can burn your skin if
touched. Allow lamp to cool for at least 5 minutes before removing. Do not operate
the UV lamp outside of the reactor. The lamp in the unit emits Ultraviolet light that
can cause permanent damage to skin and eyes. Never look at the lamp when the unit
is turned on. Handle the UV lamp by the ends only. Do not touch the bulb of a lamp
with your fingers. If the surface of the lamp becomes dirty, use a clean lint-free cloth
and glass cleaner to remove the dirt.
Your vitapur
®
UV disinfection system is equipped with a visible / audible lamp failure
indicator.IntheeventofafailureoftheUVlamp,theredLEDlightwillashanda
loud beeping will be audible from the electronic ballast of the unit. Please note that
if these conditions occur and you are on a non-municipal supplied water source, you
should immediately stop using the water for potable applications until the lamp is
replaced and disinfection of the distribution lines is completed.
Theultravioletlamphasanapproximatelifeofoneyear(9000Hrs.).Replacement
UVlampsandquartzsleevesareavailablefromanauthorizedretailerandGreenway
HomeProducts.Useonlyvitapur
®
lamps and sleeves to ensure system performance.
Replacement lamps and quartz sleeves are sold as a combined replacement kit
underthefollowingmodelnumbersandcanbeorderedonlineatgreenwayhp.com:
VUVL-2–replacementlampandquartzsleeveforVPL-2
VUVL-6–replacementlampandquartzsleeveforVPL-6
VUVL-8–replacementlampandquartzsleeveforVPL-8
VUVL-12–replacementlampandquartzsleeveforVPL-12
Procedure for Replacing / Installing the Ultraviolet (UV) Lamp:
• Turnoffthewatersupplyatbothendsofthesystem.
• Unplugtheunit.
• DrainwaterfromtheStainlessSteelUVChamber.
• Allowatleast5minutesforlamptocool.
• RemovetheconnectorfromtheendoftheUVlamp.
• RemovetheUVlampfromthequartzsleevebygentlyrotatingthelampfree.Be
sure to hold the lamp only by the ceramic tips.
• InsertthenewUVlampintothequartzsleeveandattachtheconnector.
• RelltheUVchamberbyopeningthewatersupplyjustenoughtollthechamber
with water.
• Checkthesystemforleaks.
• EnsurethattheUVlampisoperating–thegreenpowerLEDlightshouldbe
illuminated,theredlampfailureLEDlightshouldbeoffandnoaudiblealarm
should be active.
Mineral deposits and sediment build-up on the quartz sleeve will affect the system
performance by decreasing the UV light transmitted through the quartz sleeve into
the water column.
The proper maintenance and replacement of the pre-filtration required for the UV
system will reduce the accumulation of mineral and sediment residue on the quartz
sleeve.
The quartz sleeve may be cleaned with a commercially available, non-abrasive, scale
remover (should be acidic) and a lint free cloth. Cleaning of the quartz sleeve should
be done on a regular basis to ensure maximum system performance. The amount of
cleaning required will vary dependant upon local water conditions.
All traces of the cleaning solution must be fully removed from the sleeve before it is
reinstalledinthesystem.Careshouldbetakentopreventanycleaninguidfrom
coming into contact with the inside surface of the quartz sleeve.
Procedure for Removing / Installing the Quartz Sleeve:
• Turnoffthewatersupplyatbothendsofthesystem.
• Unplugtheunit.
• DrainwaterfromtheStainlessSteelUVChamber.
• Allowatleast5minutesforlamptocool.
• RemovetheconnectorfromtheendoftheUVlamp.
• RemovetheUVlampfromthequartzsleevebygentlyrotatingthelampfree.Be
sure to hold the lamp only by the ceramic tips.